Introduction |
Feasibility Study |
Ozone Levels, Permissable Safe Limits, Methods of Control
Selection of Generators |
Specifications |
Drawings |
Reference |
Schematic Drawings
Ozone Generators |
C02 Monitors |
Ozone Monitors |
VOC Monitors
Selection of Generators
OZONE GENERATOR SELECTION CHART
SELECTION PROCEDURE
Required Information:
Area to be treated.
Height (floor to suspended ceiling) of treated space.
Intended use of the space; Eg Restaurant, Bar, Lobby etc.
Number of AHU serving the space.
- Enter chart A. Plot area on the Horizontal Axis.
- Identify the Height Line in Chart A.
- Draw vertical line from point located in Step 1, to intersect with Height Line.
- Identify the closest match to Applications Line in Chart B.
- From the point located in Step 3, draw horizontal line to enter Chart B and intersect with the Applications Line.
- From this point of intersection, draw vertical line down to Horizontal Axis. Read the machine size.
- If it is between two sizes, choose larger of the two.
- If no Application Line is intersected, divide the area into multiple number of smaller areas, repeat the Selection
Procedure, and choose multiple number of generators.
EXAMPLE 1
Select Ozone Generator for a Bar.
Number of AHU is 1. Area is 2,000 Sq Ft (186 sq M). Height to ceiling is 14 Ft (4.30 M).
- Identify Height Line in Chart A. It is Line 1.
- Identify Applications Line in Chart B. It is Line 2.
- Enter area 2,000 Sq Ft on Horizontal Axis of Chart A.
- Draw vertical line to intersect with the identified Height Line (Line 1).
- From point of intersection, draw horizontal line to enter Chart B and intersect with the identified Applications Line
(Line 2).
- From point of intersection, draw vertical line down to Horizontal Axis.
- Point of intersection on Horizontal Axis is at size K8. Choose Ozone Generator K8. Qty 1 #.
EXAMPLE 2
Select Ozone Generator for a Shopping Center.
Number of AHU is 2. Area is 12,000 sq Ft (1,115 sq M). Height to ceiling is 18 Ft (5.50 M).
- Area served by each AHU is 12,000 ÷ 2 = 6,000 sq ft.
- Select Ozone Generator for each AHU.
- Interpolate Height Lines 1 and 2 to obtain point for height 18 ft.
- Identify Applications Line in Chart B. It is Line 6.
- Enter 6,000 Sq Ft on Horizontal Axis of Chart A.
- Draw vertical line to intersect with the point on Height Line as established in Step 1.
- From this point of intersection, draw horizontal line to enter Chart B, and intersect with the identified Applications
Line (Line 6).
- From point of intersection, draw vertical line down to Horizontal Axis.
- Point of intersection on Horizontal Axis is between size K4 and K5.
- Choose K5.
- Selection is K5. One Number for each AHU. Total for the Shopping Center is 2 # K5.
Introduction |
Feasibility Study |
Ozone Levels, Permissable Safe Limits, Methods of Control
Selection of Generators |
Specifications |
Drawings |
Reference |
Schematic Drawings
Ozone Generators |
C02 Monitors |
Ozone Monitors |
VOC Monitors
|